16 | VT7682S Series-Installation Guide
lockout Keypad lockout levels
Default value = 0 No lock
0 = No lock
1 = Low level
2 = Medium level
3 = High Level
Resume/
Override scheduling
ToccTime
Temporary
occupancy time
Default value = 3
hours
Temporary occupancy time with occupied mode setpoints when
override function is enabled
When the Terminal Equipment Controller is in unoccupied mode,
function is enabled with either the menu or DI1 or DI2 configured
as remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours
Cal OS
Outside air
temperature sensor
calibration
Default value = 0.0 °F
or °C
Offset that can be added/subtracted to actual displayed outside air
temperature
± 5.0 °F ( ± 2.5 °C )
2/4event
Number of events
configuration
Default value = 2
event
2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints