31 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Economizer Mode and CO2 Level Control
If the fresh air damper is to be used for both free cooling and CO2level control (econo-
mizer mode and CO2 level control, but without fresh air measurement station), only
the Min Pos, Max Pos, Min CO2and Max CO2 parameters as well as the free cooling
sequence will be active.
- The FA Range parameter should be set to 0 CFM.
- Set AI1 parameter to CO2 (0 VDC = 0ppm ; 10VDC = 2000ppm)
- Min Pos, Max Pos, Min CO2 and Max CO2 parameters should be set accord-
ing to the required setting.
The highest value between free cooling demand output and interpolation output for
the fresh air setpoint will be the output to the fresh air damper.
Current CO
2
Level
Zobrazit stránku 30
1 2 ... 26 27 28 29 30 31 32 33 34

Komentáře k této Příručce

Žádné komentáře

Country Flame Catalytic BBF Series manuales

Manuales del propietario y guías del usuario para Cocinas Country Flame Catalytic BBF Series.
Ofrecemos 1 manuales en pdf Country Flame Catalytic BBF Series para descargar gratis por tipos de documentos: Especificaciones






Más productos y manuales para Cocinas Country Flame

Modelos Tipo de documento
HR-01 Instrucciones de operaciones   Country Flame HR-01 Operating instructions [en] , 57 paginas
LR-01 Especificaciones   Country Flame LR-01 Specifications, 37 paginas
CF-04 Instrucciones de operaciones   Country Flame CF-04 Operating instructions, 58 paginas