Viconics VWZS Integration Guide Uživatelský manuál Strana 47

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 70
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 46
47
Objects Supported By Models: (VZ7000 Zoning Products)
Please refer to the specific installation guide of each controller for a detailed overview on each property listed.
Object Name
Object Type
Object Property
VZ7200F5x00W
VZ7260F5x00W
VZ7260C5x00W
VZ7656B1000W
VZ7656R1000W
VZ7656H1000W
VZ7656F1000W
VZ7656E1000W
Outdoor Temperature Override
Boolean Writable
Present Value (R,W)








Occupancy Command
Enum Writable
Present Value (R,W)








Effective Occupancy
Enum Point
Present Value (R)








Occupied Cooling Setpoint
Numeric Writable
Present Value (R,W)








Occupied Heating Setpoint
Numeric Writable
Present Value (R,W)








Unoccupied Cooling Setpoint
Numeric Writable
Present Value (R,W)








Unoccupied Heating Setpoint
Numeric Writable
Present Value (R,W)








Temporary Occupancy Time
Enum Writable
Present Value (R,W)








Thermostat Model Number
Numeric Point
Present Value (R)








Module Firmware Version Number
Numeric Point
Present Value (R)








Thermostat Firmware Version
Number
Numeric Point
Present Value (R)








RTC Smart Recovery Active
Boolean Point
Present Value (R)








TRSS
NumericSpecial
Present Value (R)








CRSS
NumericSpecial
Present Value (R)








Heartbeat Delay
NumericNoStale
Present Value (R)








Room Temperature
Numeric Writable
Present Value (R,W)



Room Temperature Override
Boolean Writable
Present Value (R,W)



Outdoor Temperature
Numeric Writable
Present Value (R,W)



Standby Cooling Setpoint
Numeric Writable
Present Value (R,W)



Standby Heating Setpoint
Numeric Writable
Present Value (R,W)



PI Cooling Demand
Numeric Point
Present Value (R)



PI Heating Demand
Numeric Point
Present Value (R)



Weighted PI Cooling Demand
Numeric Point
Present Value (R)



Zobrazit stránku 46