Viconics VWZS Integration Guide Uživatelský manuál Strana 10

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 70
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 9
10
Yellow device / node / controller have given out its 6 addresses to other devices in
building A.
Building B devices / nodes / controllers can only be connected through blue device /
nodes / controller due to maximum distance coverage.
Result:
Orange devices / nodes / controllers cannot join the ZigBee network.
Workaround to get orphan devices on the network:
Disconnect & bring one of building B device / node / controller & power it up in building
A until it joins the ZigBee network ( confirmed either at the Jace coordinator or using
the status LED on the wireless communication card of the device / node / controller.
When the device / node / controller has joined the network in building A and is added to
the Niagara database, bring it back into building B so it can propagate ZigBee
addresses to the other devices in building B.
Zobrazit stránku 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 69 70

Komentáře k této Příručce