Standard Object Types Supported
Optional
Properties
Supported
Present_Value
a,b
Out_of_Service
a
Object_Name
c
Reliability
Active_Text
Inactive_Text
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Present_Value
d
Out_of_Service
d
a : Present_Value and Out_of_Service properties are writable for every AV objects except :
PI Heating Demand (AV21)
PI Cooling Demand (AV22)
b : Present_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if
Room Temp Override (BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
c : Object_Name property is writable for the following object only :
Room Temperature (AV7)
d : Present_Value and Out_of_Service properties are writable for every MV objects except :
Output 2 (MV26)
Output 1 (MV27)
Fan Status (MV28)
Effective Occupancy (MV33)
List of Proprietary Properties
The version number of the BACnet
communications module. This is the hardware
version number
Display the MAC layer address of the module
Display the communication baud rate of the
module
Display the temperature or humidity calibration
value. The range is –5.0 deg F to 5.0 deg F for a
temperature and –15% to 15% for humidity.