VT8600 SeriesUser Interface Guide
26
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00 www.viconics.com November 2014
© 2014 Viconics Technologies. All rights reserved.
PARAMETER DETAILS SCREEN 7/9
Configuration Parameters Default Value Significance and Adjustments
Min CO2
Minimum CO2 Level
Default value: 800 ppm
Minimum CO2 Level required. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 or 100 increments
Max CO2
Maximum CO2 Level
Default value: 1200 ppm
Maximum CO2 Level allowed. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 or 100 increments